下载
Maximum leakage current, each Line to Ground:
@ 120 VAC 60 Hz: 1.4 mA
@ 250 VAC 50 Hz: 3.4 mA
Hipot rating (one minute):
Line to Ground: 1500 VAC
Neutral to Ground: 1500 VAC
Line to Neutral: 1450 VDC
Rated Voltage (max):
Phase to Phase: 440 VAC
Phase to Neutral / Ground: 250 VAC
Operating Frequency: 50/60 Hz
Rated Current: 20 to 60A
Operating Ambient Temperature Range
(at rated current I
r
): -10°C to +40°C
In an ambient t
emperat
ure (T
a
) higher than +40°C
the maximum operating current (I
o
) is calculated as
follows: I
o
= I
r
(85-Ta)/45
A Series
98
A Series
High Performance 3-phase RFI Filters for WYE Applications
Dimensions are in inches and millimeters unless otherwise specified. Values in italics
are metric equivalents. Dimensions are shown for reference purposes only.
Specifications subject to change.
Corcom Product Guide
Catalog: 1654001
Issue Date: 06.2011
For email, phone or live chat, please go to
te.com/help
corcom.com
• For 3-phase, four wire, WYE Applications
• Filters each of the three lines plus the neutral and
ground line
• Both common mode and differential mode
suppression from 50kHz to 30MHz
• Effective for both balanced and unbalanced loads
• Ground choke included
• Optional end bell kits available to shield input and
output terminals
• AYP single stage for lower noise environments
• AYT dual stage provides highest performance
Ordering Information
45 AYT 6 C
Suffix
C – Ground Choke
I
nput / Output Style
6 – Threaded 1/4 – 20 bolt
S
eries designation
AYP – Single Stage
AYT – Dual Stage
C
urrent Rating
20, 30, 45 or 60A
Specifications
Electrical Schematics
LINE
LOAD
LINE
GND
LOAD
GND
AA
B
B
C C
N
N
AYP6C Models
UL Recognized
CSA Certified
VDE Approved